Features at a glance for the ODV-2-22220-1KF12 dedicated fan and pump 2.2kW, IP20 inverter with on board RFI filter, single phase in, three phase out.
Dedicated to Centrifugal fan and pump applications, Optidrive HVAC gives powerful and flexible control in HVAC systems.
On board RFI filter
Size 2
Input Ratings
Supply Voltage
200V: 200V – 240V ± 10% 1 phase
Supply Frequency
48 – 62Hz
Power Cycles
120/hour max, evenly spaced
Output Ratings
100% output current. 10.5 Amps
Overload Capacity
110% for 60 seconds, 125% for 2 seconds
Output Frequency
Up to 120Hz
Ambient Conditions
Temperature
Storage:
-40 to 60°C
Operating:
-10 to 40°C at default switching frequency
Altitude
1000m with no derating
(derate 1%/100m above 1000m)
2000m max UL Approved
4000m max without UL Approval
Humidity
95% max, non-condensing
Enclosure
Ingress protection
Size 2 & 3: IP20 standard, IP66 optional
Size 4, 5, 6 & 7: IP55 standard
Dimensions
H= 221mm, D = 185, W = 112mm
Weight: 1.8kg
Setpoint control
(internal)
0 – 10V
10 – 0V
0 – 20mA
20 – 0mA
4 – 20mA
20 – 4mA
Motorised Potentiometer (keypad)
Modbus RTU
BACnet
Setpoint control
(optional)
Ppofibus DP
DeviceNet
BACnet/IP
I/O Specification
Digital inputs
10 – 30V DC, internal or external supply, NPN
Response time < 4ms
Power supply
24V DC, 100mA, Short Circuit protected
10V DC, 5mA for Potentiometer
Analog inputs
10 – 10V DC
0/4 – 20mA
0/24V, 30V DC max
Resolution: 12 bits + sign
Response time < 4ms
Accuracy: Better than 1% of full scale
Parameter adjustable Scaling and Offset
Analog outputs
0 – 10V
0/4 – 20mA
Relay outputs
Maximum Voltage : 250V AC, 30V DC
Switching Current : 6A AC, 5A DC
Control Features
Fire Mode: Selectable direction, Selectable speed reference
Broken belt detection: Under load monitoring with autotune configuratuion
PID Control: Internal PID control with feedback display
Hand and Auto buttons: Easily switch between keypad control and terminal control with the Hand and Auto buttons on the keypad
Pump Control Features
Pump Blockage Detection: Pump load monitoring with autotune function, user configurable
Pump Cleaning: Adjustable Pump Cleaning cycle operation
Multi-pump Control: Control of fixed speed assist pumps via optional cascade control module Control of Duty, Assist and Standby variable speed pumps via internal Master - Slave network.
Pump Stir: Automatic pump stir function
Maintenance and Diagnostics
Fault Memory: Last 4 trips stored with time stamp
Data Logging: Logging of data prior to trip for diagnostic purposes purposes: Output Current, Drive Temperature, DC Bus Voltage
Maintenance Indicator: Maintenance indicator with user adjustable maintenance interval onboard service life monitoring
Monitoring: Hours run meter, Resettable and Non-Resettable kWh meters
Product Manual
Optidrive HVAC User Manual 
£517.91 £440.22